Mains Distribution Assemblies

1600A MDA with Test Sockets

Type Ref: B7/ITC/MC1600-4P/MRCD8/MGPA12/TS

1600A icon MCCB/MCB Distribution icon Incoming MCCB 4P icon IP44 icon Free standing icon Test socket icon

£27456.04

Can’t find what you’re looking for?

We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!

MDA, 1600A 4P Incoming MCCB, 8 x MCCB/RCDs, 12W TP&N pan (see Full Description for MCCB ratings), free-standing. Fitted with test sockets to facilitate safer on-site testing.

Mains Distribution Assembly manufactured in accordance with BS EN 61439-4 designed for arduous outdoor installations. The assembly incorporates Test Sockets to facilitate safer on-site testing.

Enclosure
Robust sheet steel enclosure of seam welded construction, providing protection to IP44. The enclosure is free-standing, double-sided and incorporates a projecting rain roof, side hinged padlockable doors and removable gland plates for incoming and outgoing cables. A fully segregated compartment is provided for the MCB pan assembly. The enclosure is protected against corrosion by a high quality, outdoor finishing system comprising of a zinc phosphate pre-treatment followed by polyester powder coating, colour bright red (Vermilion, RAL 2002).
Enclosure dimensions: 1770H x 2136W x 824D mm (ground clearance 300mm).

Stand Extension
A stand extension, part number S140308SE, is available to increase the ground clearance to 900mm. The stand extension is to be ordered as a separate item.

Incoming Terminals
Fitted with a separate incoming termination chamber complete with heavy duty copper bar terminals, to enable large cross section cables to be terminated.

Incomer
Fitted a 1600A 4P MCCB, padlockable in the OFF position. The MCCB can be adjusted on site from 1600A to 640A.

Bus Bars
Fitted a bus bar system with a short circuit rating of 50 kA, based on our ASTA certified assembly.

Distribution
1 no. 800A 4P MCCB with variable Type A RCD protection. The MCCB can be adjusted on site from 800A to 320A.
1 no. 630A 4P MCCB with variable Type A RCD protection. The MCCB can be adjusted on site from 630A to 252A.
2 no. 400A 4P MCCBs each with variable Type A RCD protection. The MCCBs can be adjusted on site from 400A to 160A.
2 no. 250A 4P MCCBs each with variable Type A RCD protection. The MCCBs can be adjusted on site from 250A to 100A.
1 no. 160A 4P MCCB with variable Type A RCD protection. The MCCB can be adjusted on site from 160A to 64A.
1 no. 160A 4P MCCB with variable Type A RCD feeding an integral 12W pan assembly, which is mounted within a segregated compartment.
There are 2 no. spare MCCB ways rated at up to 250A or 1 no. way rated at 400A or 630A.

Test Sockets
In the incoming compartment, fitted with 5 no. 4.0mm panel mounted test sockets connected to the supply side of the incoming MCCB.
In each outgoing compartment, 2 no. 4.0mm panel mounted test sockets are connected to the load side of each MCCB / RCD and there is a common earth socket.
All test sockets are fixed in position and remain in-situ when inset plates are removed. They are protected by BS88 fuses.

Product Downloads

Data Sheets

Drawings

On Application

This product cannot currently be purchased online. Please contact Blakley Electrics Customer Services on 0333 188 0284 to discuss your requirements and for pricing and lead times.