Generator Connection Point comprising of a wall mounting enclosure housing a set of single pole 800A drain powerlocks, which are sequentially interlocked, ensuring that the earth connection makes first and breaks last. The 800A drain powerlocks also mate with 500A source powerlocks allowing a common GCP to be used with either rating of connector.
Please note: the largest cable that can be terminated in a cable mounted single pole connector is 300mm².